Functions:
1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic recovery
5.Voltage display(voltage measurement)
6.Current display (current measurement)
Product Parameters:
1.Model number:TVPS1-63B
2.Power supply:230VAC 50/60Hz
3.Max.Loading power:1~40A Adjustable(default:40A)
1~63A Adjustable(default:63A)
4.Over-voltage protection value range:221V~300~OFF(default:280V)
Over-voltage recovery voltage range:220V–299V(default:250V)
Over-voltage protection action time:0.1s~10s(default value:0.1s)
5.Under-voltage protection value range:219V–150V –OFF(default:160V)
Under-voltage recovery voltage range:151V–220V (default:180V)
Under-voltage protection action time:0.1s~10s(default:0.1s)
6.Over-current adjustment range:1-40A (default:40A)
Over-current action range:0.1~512 second (default:5.0s)
7.Recovery delay time 2s~120s(default:60s)
8.Power-on delay time 2s~10s(default:2s)
9.Power consumption <2W
10.Electric machinery life 100,000 times